Product description
Lead Resistance Compensation for Pt100
(Up to 5? in Each lead)
Cold-Junction Compensation for Thermocouples
(Accuracy Better than ± 0.5°C)
Measurement Accuracy : ± 0.1°C ± 0.05% of Reading
Selectable High / Low Burnout Current
(For Versions 2, 3 & 4)
Supply Voltage : 12 to 36 VDC (24 VDC Nominal)
Loop Current Output : 4 to 20 mA (Non Isolated)
Response Time :
82 mS for Version 1
250 mS for Versions 2, 3 & 4
Maximum Output Load :
[ (Vsupply – 10) / 22 ] K? (Example : 636? @ 24 VDC)
RS485 Communication Port with Free PC Software Tool for
Easy Configuration (For Versions 2, 3 & 4)